Flame Proof Walk-In Chambers

At Newtronic, We Introducing, A World class Spark free, Flame Proof Walk in Chambers, Flame proof chambers are needed for storage of aerosol, volatile, flammable liquids, reagents, chemicals and organic solvents, that meet class 1, Division 2 Criteria. These volatile substances are normally store in containers and in a controlled temperature chambers. We provide explosion proofing to all interior components of the chambers including light fittings, Motors, Control Panel, HMI, Sensors*. Our Flame proof chambers are optionally supported by FM200 Fire Suppression systems.

Request a Quote

Features

 

ETHERNET COMMUNICATION :

High-speed data transfer

Significantly faster than serial(RS-485) communication

Global standard for communication protocol

No need for a separate PC interface

Data Operations from any PC over the LAN

 

STANDBY HUMIDITY & COOLING SYSTEMS

Completely ready-to-use systems

Automatic switch-over upon failure of primary systems to achieve conditions

Scheduled & manual change-overs

Booster cooling for faster recovery

Recording of all change-overs in the software

 

COMPLETE RANGE OF ALARMS

Temperature & Humidity Deviations

Door Opening

Water Supply Failure

Component Failure

Mains Failure

 

ALARM TRANSMISSION

Mobile alert system

Time of alarm transmission

Name of equipment

Transmitted message(equipment name, alarm time, type of alarm & limits)

 

SAFETY

Temperature Overshoot/undershoot

Humidity overshoot

low water-level

Delay timer to safeguard the compressor

MCB to cut-off over current supply

Standby controlling sensor upon failure of primary

In walk-in chambers door can be open from inside

Emergency bell switch inside the chamber

 

ICDAS SOFTWARE

21 CFR Part 11 Ready

Single software suitable for upto 20 equipments

Automatic daily data back-up

Alarm logs. Alarm acknowledgement with e-signatures

Audit trails

MKT Calculations

Graphical viewing & data trending

Data export in pdf format


 

DOCUMENTATION & TRAINING

IQ, OQ, PQ

Calibration certificates

Operation & maintenance manuals

GA & electrical drawings

Material test certificates

Training to end-users

 

Galary

        

 

     

 

Specification

Temperature Range 20°C to 60°C
Temperature Accuracy ± 0.2°C
Temperature Uniformity ± 1°C
Humidity Range 40% RH to 95% RH
Humidity Accuracy ± 2% RH
Humidity Uniformity ± 3% RH

 

Standard Equipment

 

Double walled with 80mm PUF insulated modular panels with easy on-site assembly System is made up of split type condenser unit in well-ventilated area to avoid throw of hot air in the room
SS 304 Interior & Exterior either SS 304 or Powder Coated G.I. Stand by humidity system
Stainless Steel Trays Complete Operations driven through PLC with data logging capacity of upto 1000 readings & email facility
Observation window - 300 x 300 mm High speed Ethernet based communication
Illuminated working area All operations through a single 4" Color Touch Screen
U-shaped SS tubular heaters High-quality German Make temperature humidity sensor with 4-20mA output
Flooring of Linoleum carpet Safety devices: Low & High temperature cut-off settable thermostats & high humidity cut-off device
Forced air circulation for uniform temperature Audio/Visual alarms for deviations
Non Condensing steam injection type humidity system with standby heater & auto switch overs Complete with IQ, OQ, PQ & Operations & Maintenance Manual
CFC free cooling system consisting of hermetically sealed compressor coupled with evaporation coil & condenser

 

Optional Accessories

 

ICDAS - A Common Software suitable for 20 nos. Newtronic make equipments Door Access system
8pt. Temperature & Humidity Scanners Mobile Alert system
Stand by Cooling System with auto switch overs Remote alarm system suitable for 4 nos. Newtronic make equipments

 

Selection Guide

 

Models
Capacity
Internal Chamber
External Chamber
Tray Size
Trays
Cuft.
Litres
HxWxD (mm)
HxWxD (mm)
(mm)
Nos.
NEPL 2190RSI 190 5400 2000x1360x2000 2120x1480x2120 870x300 24
NEPL 2230RSI 230 6400 2400x1360x2000 2520x1480x2120 870x300 32
NEPL 2280RSI 280 8000 2000x2000x2000 2120x2120x2120 870x600 24
NEPL 2340RSI 340 9600 2400x2000x2000 2520x2120x2120 870x600 32
NEPL 2428RSI 428 12000 2400x2500x2000 2520x2620x2120 870x800 32
NEPL 2530RSI 530 15000 2400x2500x2500 2520x2620x2620 725x800 48
NEPL 2640RSI 640 18000 2400x2500x3000 2520x2620x3120 900x800 48
 